¡ñ products
¡ñ device
¡ñ installation
¡ñ FAQ
Desiccant Dehumidification Rotors
Chinese





»ØÊ×Ò³

Frequent Asked Questions and Solutions

1 System is over water supply
   To control the water supply by adjusting the valve or change to the water pump with lower power.

2 Non-evenness of the water spreading on the paper pad
    To check the installation is under the correct way or not. Adjust valve to control the water supply; Change the water pump with more power or water pipe with high caliber. Clean the pool, pump entrance, filter and pipe etc. in time. Eliminate the dirt inside the water recycling system.

3 leaking treatment
    To check whether water is over supply, pad is damaged, dilapidated on the edge or leaking at the connection. Use silicon glue to plug after water supply stops.

4 Pad cleaning
    Elimination of the scale and alga on pad's surface: Use the soft brush to remove up and down after the pad's completely drying out. Do not remove horizontally. (Can brush a small part to verify if the pad stand or not). Then only switch on the water supply system to wash the scale and alga on pad's surface. (Do not use steam or high pressure water)

 
Maintenance of the SAT

1 Daily maintenance
    Turn off the exhaust fans after 30min of the pump stopped to make sure the complete dry of the pad. To check if all empty in the bottom frame after system stopped to avoid the pad bottom is dipped in the water all the time.

2 Water quality control
    The pool must be sealed with a cover. Keep the water resource clean. The ph value should be between 6 ¨C 9 and the electric conductance should be less than 1000 micro-ohm. Clean the pool and water recycling system regularly to assure the cleanness of water supply system. (usually once a week). Maintain the good quality of the water supply. To prevent alga and other microbe from spreading the SAT, two measures can be adopted: put in 3-5ppm Chlorine or Bromine for short time treatment or 1ppm for continuous processing.

3 Rats prevention
    Can install rats defense or use rats killing spray at the bottom of the pad when not in use